Hero Banner

Welcome to Our Company

Explore the best products from top brands

Control & Monitoring: DCS, ESD. SCADA, HMI, PLC

All products

FX2N-2LC

$208.80

FX2N-2LC -- Mitsubishi Electric -- Temperature adjustment block


• Estimated Lead Time : In stock. Usually ships in 7-10 working days

• Manufacturer : Mitsubishi Electric

• Temperature adjustment block FX2N-2LC

• Temperature sensor, temperature controlNumber of input points2 points

• Type of inputthermocoupleK, J, R, S, E, T, B, N, PLII, WRe 5-26, U, L JIS C 1602-1995

• Resistance temperature detector3-wire type Pt100 JIS C 1604-1997 (new JIS) JPt 100 JIS C 1604-1981 (old JIS)

• Measurement accuracyAmbient temperature 23 掳 C 卤 5 掳 C: Input range 卤 0.3% 卤 1 digit Ambient temperature 0 掳 C to 55 掳 C: Input range 卤 0.7% 卤 1 digit However, B input 0 to 399 掳 C (0 to 799 掳 F) and PLII , 0 to 32 掳 F of WRe5-26 input is out of guaranteed accuracy range

• Cold junction temperature compensation errorWithin 卤 1.0 掳 C. However, the input value is within 卤 2.0 掳 C at -150 to -100 掳 C, and 卤 3.0 掳 C at -200 to -150 掳 C.

• resolution0.1 掳 C (0.1 掳 F) or 1 掳 C (1 掳 F) Depends on the input range of the sensor used.

• Sampling period500 ms

• Influence of external resistanceAbout 0.35 渭V / 惟

• Input impedance1 M惟 or more

• Sensor currentAbout 0.3 mA

• Permissible input wire resistance10 惟 or less

• Operation at input break / short circuitUpscale / downscale

• Current detector (CT) input (number of inputs)2 points

• Current detector (CT) input (current detector)CTL-12-S36-8 or CTL-6-PH (made by usd)

• Current detector (CT) input (heater current measurement value)When using CTL-12: 0.0 to 100.0 A When using CTL-6: 0.0 to 30.0 A

• Current detector (CT) input (measurement accuracy)卤 5% of the input value or 2A, whichever is larger (excluding the accuracy of the current detector)

• Current detector (CT) input (sample period)1 second

• control methodTwo position control, PID control (with auto tuning function), PI control

• Control operation cycle500 ms

• Measurement temperature rangeK-200.0 to 200.0 掳 C, -100.0 to 400.0 掳 C, -100 to 1300 掳 C, -100 to 800 掳 F, -100 to 2400 掳 F

• J-200.0 to 200.0 掳 C, -100.0 to 400.0 掳 C, -100.0 to 800.0 掳 C, -100 to 1200 掳 C, -100 to 1600 掳 F, -100 to 2100 掳 F

• T-200.0 to 200.0 掳 C, -200.0 to 400.0 掳 C, 0.0 to 400.0 掳 C, -300.0 to 400.0 掳 F, -300.0 to 700.0 掳 F, 0.0 to 700.0 掳 F

• S0 to 1700 掳 C, 0 to 3200 掳 F

• R0 to 1700 掳 C, 0 to 3200 掳 F

• E-200.0 to 200.0 掳 C, 0 to 1000 掳 C, 0 to 1800 掳 F

• B0 to 1800 掳 C, 0 to 3000 掳 F

• N0 to 1300 掳 C, 0 to 2300 掳 F

• PLII0 to 1200 掳 C, 0 to 2300 掳 F

• Wre5-260 to 2300 掳 C, 0 to 3000 掳 F

• U-200.0 to 600.0 掳 C, -300.0 to 700.0 掳 F

• L0.0 to 900.0 掳 C, 0 to 1600 掳 F

• JPt100-50.0 to 150.0 掳 C, -200.0 to 500.0 掳 C, -300.0 to 300.0 掳 F, -300 to 900 掳 F

• Pt100-50.0 to 150.0 掳 C, -200.0 to 600.0 掳 C, -300.0 to 300.0 掳 F, -300 to 1100 掳 F

• Heater burnout detectionAlarm is detected by setting buffer memory (variable in the range of 0.0 to 100.0 A)

• Operation mode0: Measured value monitor 1: Measured value monitor + temperature alarm 2: Measured value monitor + temperature alarm + control (selected by buffer memory)

• Self-diagnosis functionBy adjustment data check, input value check, watchdog timer. Transistor output OFF when abnormality detected

• memoryBuilt-in EEPROM (number of rewrites: 100,000 times)

• Insulation method路 Insulation between analog input unit and sequencer by photo coupler 路Insulation between analog input unit and power supply by DC / DC converter 路 Insulation between channels

• I / O occupancy points8 points (can be counted either input or output)

• Applicable sequencerFX2N, FX3U, FX2NC, FX3UC Connection to FX2NC requires FX2NC-CNV-IF. Connection to FX3UC requires FX2NC-CNV-IF or FX3UC-1PS-5V.

• mass0.3 kg

• Output specification

• Output points2 points

• Output methodNPN open collector transistor output

• Rated load voltageDC5-24V

• Maximum load voltageDC30V or less

• Maximum load current100 mA

• OFF leakage current0.1 mA or less

• Maximum voltage drop when ONWhen 2.5V (max), 1.0V (TYP) 100mA is energized

• Control output cycle30 seconds (variable from 1 to 100 seconds)

• Power supply specification

• Power supply5VDC 70mA ( internal power supply from sequencer) 24VDC + 10% -15% 55mA (external power supply)

• Ambient temperature0 to 55 掳 C 路 路 路 路 -25 to 75 掳 C 路 路 路 路 路 路

• Relative humidity5 to 95% RH (without condensation)

• Vibration resistanceWhen mounting DIN railFrequency: 10 to 57 HzSingle amplitude: 0.035 mm X, Y, Z each direction 10 times (total 80 minutes each)

• Frequency: 57 to 150 HzAcceleration: 4.9 m / s 2 X, Y, Z each direction 10 times (total 80 minutes each)

• Direct mountingFrequency: 10 to 57 HzSingle amplitude: 0.075 mm X, Y, Z each direction 10 times (total 80 minutes each)

• Frequency: 57 to 150 HzAcceleration: 9.8 m / s 2 X, Y, Z each 10 times (total 80 minutes each)

• Shock resistance147 m / s 2 , action time 11 ms, sine half-wave pulse 3 times in X, Y, Z directions

• Noise resistantNoise voltage: 1,000 Vp-p, noise width: 1 渭s, rise time: 1 ns, period: 30 to 100 Hz noise simulator

• Withstand voltageBetween analog input terminal and ground terminal: AC500V 1 minute

• Insulation resistanceBetween analog input terminal and ground terminal: 5 M惟 or more with DC 500 V insulation resistance tester

• groundType D Grounding (Grounding resistance: 100 惟 or less) < Do not connect to a common ground with a high-power system> Connect a dedicated ground or shared ground.

• Use atmosphereCorrosive, no flammable gas, no severe conductive dust (dust)

• Use altitudeIt can not be used in an environment pressurized to 2000 m or less at atmospheric pressure or higher. There is a possibility of breakdown.

• Shipping Weight : 2 Kg