FX2N-32MT-ES/UL
$407.70
FX2N-32MT-ES/UL --Mitsubishi Electric -- Fx2n Series Programmable Controllers
• Estimated Lead Time: 5-7 Working Days
• Manufacturer: Mitsubishi Electric
• FX2N-32MT-ES/UL
• The arithmetic and control system : Stored program repeat operation method (dedicated LSI), there interrupt instruction
• Input and output control method : Batch processing method (END when the instruction is executed), input and output refresh command, Pulse catch function
• Programming language : Relay symbol system + step ladder system (SFC representation Allowed)
• Program memory : The maximum memory capacity : 16000 step聽 comment, 16000 steps, including the file register
• Built-in memory capacity and format : 8000 step RAM (backed up by a built-in lithium battery)
• Memory cassette (memory board) : 路 FX-RAM-8 (2000/4000/8000/16000 step correspondence possible)聽 路 FX-EPROM-8 (2000/4000/8000/16000 step correspondence possible)聽 路 FX-EEPROM-4 (2000/4000 step correspondence possible)聽 路 FX-EEPROM-8 (2000/4000/8000 step correspondence possible)聽 路 FX-EEPROM-16 (2000/4000/8000/16000 step correspondence possible)
• Function Expansion Memory (function expansion memory board) : The sequencer version V3.00 or higher, FX2N-ROM-E1 form function expansion memory board can be mounted聽 short-mail transmission function聽 inverter operation control function聽 -16000 step EEPROM (2000/4000/8000 step also correspondence possible)
• RUN during the write function : Yes (can change programs during the sequencer RUN)
• Protective function : There is password protection function (by keyword function)
• Real-time clock : Clock function : Built聽 from 1980 to 2079 years (with leap year correction) The year 2-digit / 4-digit switch, monthly deviation 卤 45 seconds (25 掳C)
• Type of instruction : Basic instruction : Sequence Instruction: 27聽 -step ladder instructions: two
• Application Instructions : Application Instructions: 132 species
• Arithmetic processing speed : Basic instruction : 0.08渭s / instruction
• Application Instructions : 1.52 to the number of 100渭s / instruction
• Input and output points : Number of inputs : 184 points or less (at the time of expansion in combination)
• Number of outputs : 184 points or less (at the time of expansion in combination)
• Remote I / O points (CC-Link) : Following the actual I / O, including 256 points
• Total score : Less than 256 points (at the time of expansion in combination)
• device : Input and output relay : Input relay : X000 ~ X267 184 points (octal number) extension when used with
• Output relay : Y000 ~ Y267 184 points (octal number) extension when used with
• Auxiliary relay : For general use : M0 ~ M499 500 points聽 is a non-battery backup area.聽You can change the battery backup area by the parameter setting.
• For Keep : M500 ~ M1023 524 points聽 is a battery back-up area.聽You can change to a non-battery backup area by the parameter setting.
• For Keep (battery backup fixed area) : M1024 ~ M3071 2048 points聽 is the battery backup fixed area.聽This area is characteristic not be changed.
• For special : M8000 ~ M8255 256 points
• State : Initial state : S0 ~ S9 10 points
• For general use : S10 ~ S499 490 points聽 is a non-battery backup area.聽You can change the battery backup area by the parameter setting.
• For Keep : S500 ~ S899 400 points聽 is a battery back-up area.聽You can change to a non-battery backup area by the parameter setting.
• For annunciator : S900 ~ S999 100 points聽 is a battery back-up area.聽You can change to a non-battery backup area by the parameter setting.
• Timer (on-delay) : 100ms : T0 ~ T199 200 points (0.1 to 3,276.7 seconds)
• 10ms : T200 ~ T245 46-point (0.01 to 327.67 seconds)
• 1ms integration type (capacitor keep) : T246 ~ T249 4 points (0.001 to 32.767 seconds)聽 is a battery-backed fixed area.聽This area is characteristic not be changed.
• 100ms integration type (capacitor keep) : T250 ~ T255 6 points (0.1 to 3,276.7 seconds)聽 is a battery-backed fixed area.聽This area is characteristic not be changed.
• counter : 16-bit up : C0 ~ C99 100 points (0 to 32,767 counts)聽 is a non-battery backup area.聽You can change the battery backup area by the parameter setting.
• 16-bit up (battery backup area) : C100 ~ C199 100 points (0 to 32,767 counts)聽 is a battery back-up area.聽You can change to a non-battery backup area by the parameter setting.
• 32-bit bi-directional : C200 ~ C219 20 points (-2,147,483,648 ~ + 2,147,483,647 count)聽 is a non-battery backup area.聽You can change the battery backup area by the parameter setting.
• 32-bit bi-directional (battery backup area) : C220 ~ C234 15 points (-2,147,483,648 ~ + 2,147,483,647 count)聽 is a battery back-up area.聽You can change to a non-battery backup area by the parameter setting.
• High-speed counter : [32-bit high-speed up / down]聽 C235 ~ C255 maximum six points usable in聽 one phase: 60KHz, 10KHz聽 2 phase: 30kHz, 5kHz聽 There is a limit to the number and input frequency that can be used by the conditions used.聽 It is a battery backup area.聽You can change to a non-battery backup area by the parameter setting.
• Data register (32-bit in the pair used) : 16-bit general purpose : D0 ~ D199 200 points聽 is a non-battery backup area.聽You can change the battery backup area by the parameter setting.
• 16 bit for Keep (battery backup area) : D200 ~ D511 312 points聽 is a battery back-up area.聽You can change to a non-battery backup area by the parameter setting.
• 16 bit for Keep (battery backup fixed area) : D512 ~ D7999 7488 points (D1000 later, Allowed set to file register in the 500-point unit) is a battery backup fixed area.聽This area is characteristic not be changed.
• 16 bit for special : D8000 ~ D8255 256 points
• For 16-bit index : V0 ~ V7, Z0 ~ Z7 16 points
• Pointer : JUMP, for CALL branch : P0 ~ P127 128 points (CJ instruction, for the CALL instruction, for the END jump P63)
• Input interrupt : I00 ??~ I50 ??6 points
• Timer interrupt : I6 鈻♀枴 ~ I8 鈻♀枴 3 points
• Counter interrupt : I010 ~ I060 6 points (for HSCS instruction)
• nesting : [Master control]聽 N0 ~ N7 8 points (for MC instruction)
• constant : Decimal number (K) : 16-bit: -32,768 + 32,767聽 32-bit: -2,147,483,648 ~ + 2,147,483,647
• Hexadecimal (H) : 16-bit: 0 ~ FFFF聽 32 bit: 0 ~ FFFFFFFF
• Power Specifications : 聽
• Rated voltage : AC100 ~ 240V
• Allowable voltage range : AC85 ~ 264V
• Rated frequency : 50 / 60Hz
• Allowable momentary power failure time : 10ms will continue to operate for the momentary power failure follows.聽 If the power supply voltage is AC200V system, by the user program, you can change it to 10 ~ 100ms.
• Power Fuse : 250V 3.15A (3A)
• Inrush current : Maximum 40A 5ms or less / AC100V, maximum 60A 5ms or less / AC200V
• Power consumption : 30W
• DC24V service power : 250mA or less
• DC5V internal supply power supply : 290mA
• Input Specifications : 聽
• Number of inputs : 16 points
• Input connection shape : Removable terminal block (M3 screws)
• Input format : sink
• Input signal voltage : DC24V 卤 10%
• Input impedance : X000 ~ X007 : 3.3k惟
• X010 or later : 4.3k惟
• Input signal current : X000 ~ X007 : 7mA / DC24V
• X010 or later : 5mA / DC24V
• Input ON sensitivity current : X000 ~ X007 : More than 4.5mA
• X010 or later : More than 3.5mA
• Input OFF sensitivity current : 1.5mA or less
• Input response time : About 10Ms聽 X000 ~ X017 (to basic unit built-in number) it has a built-in digital filter, can be changed in 1ms unit to 0 ~ 60ms depending on the application instructions or D8020.聽 If 0 is specified, X000, X001 is 20渭s, X002 ~ X017 will be 50渭s.
• Input signal format : No-voltage contact input聽 NPN open collector transistor
• Input circuit insulation : Photocoupler
• Input Operation Display : Input ON when the LED lights up
• Output Specifications : 聽
• Number of outputs : 16 points
• Output connection shape : Removable terminal block (M3 screws)
• Output type / format : Transistor / sink output
• External power supply : DC5 ~ 30V
• Peak load : Resistance load : Output 1 point / common: 0.5A or less聽 output 4 points / common: 0.8A or less聽 Output 8 points / common: 1.6A or less聽 (Y000, Y001 is, 0.3A / output 1 point)
• Inductive load : 12W / DC24V (Y000, Y001 is 7.2W / DC24V)
• Minimum load : -
• Open circuit leakage current : 0.1mA / DC30V
• ON voltage : 1.5V
• Response time : OFF ??ON : Y000, Y001: 15渭s following聽 Y002 later: 0.2ms or less
• ON ??OFF : Y000, Y001: 30渭s following聽 Y002 later: 0.2ms or less
• Circuit insulation : Photocoupler
• Output operation display : Photocoupler drive when LED lighting
• Built-in high-speed counter function : 聽
• 1 phase 1 count input : [C235, C236]聽 up to two points: the best 60kHz聽 high speed compared to SET / RESET when using: 10kHz聽 high-speed bandwidth comparing HSZ use at the time: 5.5KHz聽 [C237 ~ C245]聽 up to 4 points: up to 10kHz聽 high speed compared to SET / RESET when using: 10kHz聽 high speed bandwidth comparing HSZ use at the time: 5.5kHz聽 high-speed counter, pulse output instruction, the sum of the frequency at which the sequencer pulse density instruction processing (2-phase counter are totaled twice the input frequency) is a 20kHz maximum.聽 During the high-speed comparison SET / RESET use, high-speed counter, pulse output instruction, the sum of the frequency at which the sequencer pulse density instruction processing (2-phase counter are totaled twice the input frequency) is the maximum 11kHz is.聽 High-speed counter, pulse output instruction, the sum of the frequency at which the sequencer processes a pulse density instruction (the two-phase counter summing up the 2 times the input frequency), 5.5kHz is the maximum.
• 1-phase 2-count input : [C246]聽 up to one point: the best 60kHz聽 high speed compared to SET / RESET when using: 10kHz聽 high-speed bandwidth comparing HSZ use at the time: 5.5KHz聽 [C247 ~ C250]聽 up to two points: the best 10kHz聽 high speed compared to SET / RESET when using: 10kHz聽 high-speed bandwidth comparing HSZ use at the time: 5.5kHz聽 high-speed counter, pulse output instruction, the sum of the frequency at which the sequencer pulse density instruction processing (2-phase counter are totaled twice the input frequency) is a 20kHz maximum.聽 During the high-speed comparison SET / RESET use, high-speed counter, pulse output instruction, the sum of the frequency at which the sequencer pulse density instruction processing (2-phase counter are totaled twice the input frequency) is the maximum 11kHz is.聽 High-speed counter, pulse output instruction, the sum of the frequency at which the sequencer processes a pulse density instruction (the two-phase counter summing up the 2 times the input frequency), 5.5kHz is the maximum.
• 2-phase 2-count input : [C251]聽 up to one point: the best 30kHz聽 high speed compared to SET / RESET when using: 5kHz聽 high-speed bandwidth comparing HSZ use at the time: 4kHz聽 [C252 ~ C255]聽 up to two points: the best 5kHz聽 high speed compared to SET / RESET when using: 4kHz聽 high-speed bandwidth comparing HSZ when using: 4kHz聽 high-speed counter, pulse output instruction, the sum of the frequency at which the sequencer pulse density instruction processing (2-phase counter are totaled twice the input frequency) is a 20kHz maximum.聽 During the high-speed comparison SET / RESET use, high-speed counter, pulse output instruction, the sum of the frequency at which the sequencer pulse density instruction processing (2-phase counter are totaled twice the input frequency) is the maximum 11kHz is.聽 High-speed counter, pulse output instruction, the sum of the frequency at which the sequencer processes a pulse density instruction (the two-phase counter summing up the 2 times the input frequency), 5.5kHz is the maximum.
• Built-in pulse output and positioning function : 聽
• Number of controlled axes : Independent 2-axis
• Maximum frequency : 20kHz
• Programming language : Sequence program
• Corresponding basic unit : Transistor output type basic unit
• Pulse output instruction : Pulse output (PLSY)聽 , acceleration and pulse output with speed (PLSR)聽 pulse output format: pulse train (the direction is controlled by the sequence)
• Positioning instruction : 路 ABS current value read ([D] ABS)聽 corresponding with V3.00 or more
• Ambient temperature 0 ~ 55 掳C 路路路路路 operation, -20 ~ 70 掳C 路路路路路 during storage
• Relative humidity 35 ~ 85% RH (non-condensing) ..... operation
• Vibration resistance When the DIN rail mounting Frequency: 10 ~ 57Hz Half amplitude: 0.035mm X, Y, Z each direction 10 times (for a total of each 80 minutes)聽 criteria, according to IEC61131-2
• Frequency: 57 ~ 150Hz Acceleration: 4.9M / S聽2銆�X, Y, Z each direction 10 times (for a total of each 80 minutes)聽 criteria, according to IEC61131-2
• Direct mounting at the time Frequency: 10 ~ 57Hz Half amplitude: 0.075mm X, Y, Z each direction 10 times (for a total of each 80 minutes)聽 criteria, according to IEC61131-2
• Frequency: 57 ~ 150Hz Acceleration: 9.8M / S聽2銆�X, Y, Z each direction 10 times (for a total of each 80 minutes)聽 criteria, according to IEC61131-2
• Impact 147M / S聽2聽, action time 11ms, X at half-sine pulse, Y, Z 3 times each direction聽 criterion, according to IEC61131-2
• Anti-noise Noise voltage 1,000Vp-p, noise width 1渭s, due to rising 1ns, cycle 30 ~ 100Hz of noise simulator
• Withstand voltage When performing a withstand voltage test, please go between the ground terminal of each terminal and the basic unit at a voltage of below.聽 Power supply terminal (AC power) and between the ground terminal: AC1.5kV 1 minute聽 DC24V service power supply, and the input terminal (DC24V) and between the ground terminal: AC500V 1 minute聽 output terminal (transistor) and between the ground terminal: AC500V 1 minute
• Insulation resistance When performing the insulation resistance test, please go between the ground terminal of each terminal and the basic unit at a voltage of below.聽 Power supply terminal (AC power) and between the ground terminal: DC500V 5M惟 more in insulation resistance tester聽 DC24V service power supply, and the input terminal (DC24V) and between the ground terminal: DC500V 5M惟 more in insulation resistance tester聽 and the output terminal (transistor) ground terminal between: DC500V 5M惟 more in insulation resistance tester
• ground Class D grounding (ground resistance: 100惟 or less) <common ground is not allowed with the high-voltage system>聽 ground, please dedicated ground or shared ground.
• Use atmosphere Corrosive, there is no flammable gas, conductive dust (dust) that is not terribly
• Advanced use 2000m or less聽 can not be used in the pressurized environment to more than atmospheric pressure.There is a possibility of failure.
• Shipping Weight: 1.65 Kg