Hero Banner

Welcome to Our Company

Explore the best products from top brands

Control & Monitoring: DCS, ESD. SCADA, HMI, PLC

All products

FX3S-30MT/ES

$299.70

FX3S-30MT/ES-- Mitsubishi Electric -- FX 3 S series FX 3 S - 30 MT / ES


• Estimated Lead Time : In stock. Usually ships in 7-10 working days.

• Manufacturer : Mitsubishi Electric

• FX3S-30MT/ES

• FX 3 S series FX 3 S - 30 MT / ES

• Arithmetic control method\n: Stored program iterative calculation method with interrupt instruction\n

• Input / output control method\n: Batch processing method (when END instruction is executed), I / O refresh command, with pulse catch function\n

• Programming language\n: Relay symbol method + step ladder method (SFC expressible)\n

• Program memory Maximum memory capacity\n: 16000 steps Comment, 16000 steps including file register\n

• Program memory Internal memory capacity / format\n: 16000 steps EEPROM (memory backup not required)\n

• Program memory Memory cassette (option)\n: FX3G-EEPROM-32L connectable (32000 step EEPROM)\nFX3S series can be used up to 16000 steps (program capacity is 4000 steps)\n

• Program memory Write function during RUN\n: Yes (program changeable during sequencer RUN)\n

• Program memory Protection function\n: Keyword protection function / With customer keyword function\n

• Real time clock: -

• Clock function\n: Built-in\n1980 to 2079 (with leap year correction) 2-digit / 4-digit year AD changeable, monthly difference 卤 45 seconds (25 掳 C)\n? Note on clock function\nThe current time of the built- It is backed up with.\nThe large capacity condenser (built-in) is fully charged at the energization time of 30 minutes and holds the present value for 10 days.\n

• Types of instructions: -

• Basic instruction\n: 路 Sequence instruction: 29 pieces\n路 Step ladder instruction: 2 pieces\n

• Application instruction\n: Application instruction: 116 kinds\n

• Arithmetic processing speed: -

• Basic instruction\n: 0.21 碌s / instruction\n

• Application instruction\n: 0.5 碌s to several 100 碌s / instructions\n

• Number of input / output points: -

• Number of input points\n: 16 points or less (can not be added)\n

• Number of output points\n: 14 points or less (can not be added)\n

• Total score\n: 30 points or less (can not be added)\n

• device: -

• I / O relay Input relay\n: X000 to X017 16 points (octal number) can not be added\n

• Output relay\n: Y000 to Y015 14 points (octal number) can not be added\n

• Auxiliary relay For general use 1\n: M 0 to M 383 384 points\n

• Keep (EEPROM keep)\n: M384 to M511 128 points\n? Note on\nkeeping area Keep area and nonkeeping area are fixed. (Parameter can not be changed.) In\norder to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.\n

• For general use 2\n: M512 to M1535 1024 points\n

• Special purpose\n: M8000 to M8511 512 points\n

• State For initial state (EEPROM keep)\n: S0 to S9 10 points\n? Note on\nkeeping area Keep area and nonkeeping area are fixed. (Parameter can not be changed.) In\norder to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.\n

• Keep (EEPROM keep)\n: S10 to S127 118 points\n? Note on\nKeep Area Keep area and non-keep area are fixed. (Parameter can not be changed.) In\norder to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.\n

• For general use\n: S128 to S255 128 points\n

• Timer (on-delay) 100 ms\n: T 0 to T 31 63 points (0.1 to 3,276.7 seconds)\n

• 100 ms / 10 ms\n: T32 to T62 31 points (0.1 to 3,276.7 seconds / 0.01 to 327.67 seconds)\nT32 to T62 (31 points) can be changed to 10 ms timer when M8028 is turned ON\n

• 1 ms\n: T63 to T127 65 points (0.001 to 32.767 seconds)\n

• 1 ms integration type\n: T128 to T131 4 points (0.001 to 32.767 seconds)\n

• 100 ms Integration type\n: T132 to T137 6 points (0.1 to 3,276.7 seconds)\n

• Other\n: Two internal analog volume can be used as analog timer VR 1: D 8030, VR 2: D 8031 ??2 points (0 to 255)\n

• counter 16 bit up (for general purpose)\n: C 0 to C 15 16 points (0 to 32,767 counts)\n

• 16 bit up (EEPROM keep)\n: C16 to C31 16 points (0 to 32,767 counts)\n* Note on\nkeep area Keep area and non-keep area are fixed. (Parameter can not be changed.) In\norder to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.\n

• 32 bit up / down\n: C200 to C234 35 points (-2, 147, 483, 648 to +2, 147, 483, 647 counts)\n

• High speed counter\n: [32 bit high-speed up / down (EEPROM keep)]\nUp to 6 points can be used in C235 to C255\n1 phase: 60 kHz, 10 kHz\n2 phases: 30 kHz, 5 kHz\nThere are restrictions on points and input frequencies that can be used depending on the conditions used.\n? Note on\nKeep Area Keep area and non-keep area are fixed. (Parameter can not be changed.) In\norder to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.\n

• Data register (32 bits in pair use) For 16-bit general purpose 1\n: D0 to D127 128 points\n

• For 16-bit keep (EEPROM keep)\n: D128 to D255 128 points\n? Note on the\nkeep area Keep area and non-keep area are fixed. (Parameter can not be changed.) In\norder to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.\n

• For 16-bit general purpose 2\n: D256 to D2999 2744 points\n

• File register (EEPROM keep)\n: D1000 to D2999 2000 points (It can be set to the file register in units of 500 points)\n

• 16 bit special use\n: D 8000 to D 8511 512 points\n

• For 16 bit index\n: V 0 to V 7, Z 0 to Z 7 16 points\n

• Pointer JUMP, for CALL branch\n: P0 to P255 256 points (for CJ instruction, CALL instruction, P63 for END jump)\n

• Input interrupt\n: I 0 ? ? - I 5 ? ? 6 points\n

• Timer interrupt \n: I6 ?? - I 8 ? ? 3 points\n

• nesting\n: [For master control]\nN 0 to N 7 8 points (for MC command)\n

• Constant Decimal number (K)\n: 16 bits: -32,768 to + 32,767\n32 bits: -2, 147, 483, 648 to +2, 147, 483, 647\n

• Constant Hexadecimal (H)\n: 16 bits: 0 to FFFF\n32 bits: 0 to FFFFFFFF\n

• Constant Real number (E)\n: 32 bits: -1.0 脳 2 128 to -1.0 脳 2 - 126 , 0, 1.0 脳 2 - 126 to 1.0 脳 2 128\nDecimal point representation and exponential representation are possible\n

• Power supply specification\n:\n

• Rated voltage\n: AC 100 to 240 V\n

• Voltage tolerance range\n: AC 85 - 264 V\n

• Rated frequency\n: 50/60 Hz\n

• Allowable momentary power outage time\n: Operation continues with an instantaneous blackout of 10 ms or less.\n

• Power supply fuse\n: 250V 1A\n

• Inrush current\n: Maximum 15 A 5 ms or less / AC 100 V, 28 A maximum 5 ms or less / AC 200 V\n

• power consumption\n: In\nthe case of the maximum configuration that can be connected to the 21 W basic unit, this is the value when using 24 VDC service power.\nIt also includes input current (7 mA or 5 mA per point).\n

• 24 VDC service power supply\n: 400 mA\n

• Input specification\n:\n

• Number of input points\n: 16 points\n

• Input connection shape\n: Fixed terminal block (M3 screw)\n

• Input format\n: Sink / source\n

• Input signal voltage\n: DC 24 V 卤 10%\n

• Input impedance: -

• X000 to X007\n: 3.3 kO\n

• X010 or later\n: 4.3 kO\n

• Input signal current: -

• X000 to X007\n: 7 mA / 24 VDC\n

• X010 or later\n: 5 mA / 24 VDC\n

• Input ON sensitivity current: -

• X000 to X007\n: 4.5 mA or more\n

• X010 or later\n: 3.5 mA or more\n

• Input OFF sensitivity current\n: 1.5 mA or less\n

• Input response time\n: Approximately 10 ms\nX000 to X017 have a built-in digital filter and can be changed in 1 ms increments to 0 to 15 ms according to application instructions and D8020. However, when set to 0, it becomes the following.\nX000, X001: 10 .mu.s\nX002 to X007: 50 .mu.s\nX010 to X017: 200 .mu.s\n

• Input signal format\n: No-voltage contact input At\nsink input: NPN open collector transistor\nSource input: PNP open collector transistor\n

• Input circuit insulation\n: Photocoupler insulation\n

• Input operation display\n: LED on the panel when driving the photo coupler\n

• Number of output points\n: 14 points\n

• Output connection shape\n: Fixed terminal block (M3 screw)\n

• Output type / format\n: Transistor / sink output\n

• External power supply\n: DC 5 to 30 V\n

• Maximum load: -

• Resistive load\n:\nThe total load current per 0.5 A / point common should be as follows.\nOutput 1 point / common: 0.5 A or less\nOutput 4 points / common: 0.8 A or less\n

• Inductive load\n: The total load per 12 W / DC 24 V common should be as follows.\nOutput 1 point / common: 12 W or less / 24 VDC\noutput 4 points / common: 19.2 W or less / 24 VDC\n

• Minimum load\n: -\n

• Open-circuit leakage current\n: 0.1 mA or less / DC 30 V\n

• ON voltage\n: 1.5V or less\n

• Response time: -

• OFF ? ON\n: Y000, Y001: 5 碌s or less / 10 mA or more (DC 5 to 24 V)\nY002 to Y015: 0.2 ms or less / 200 mA or more (DC 24 V)\n

• ON ? OFF\n: Y000, Y001: 5 碌s or less / 10 mA or more (DC 5 to 24 V)\nY002 to Y015: 0.2 ms or less / 200 mA or more (DC 24 V)\n

• Circuit insulation\n: Photocoupler insulation\n

• Output operation indication\n: LED on the panel surface when photo coupler is driven\n

• Built-in high speed counter function\n:\n

• 1 phase 1 count input\n: [C235, C236]\n60 kHz [C237\nto C240]\n10 kHz\n[C241]\n60 kHz\n[C242 to C245]\n10 kHz When\nusing multiple high-speed counters, make sure that the total of operating frequencies is less than the total frequency.\n

• 1 phase 2 count input\n: [C246]\n60 kHz [C248\n(OP)]\n10 kHz\n[C247 to C250]\n10 kHz When\nusing multiple high-speed counters, make sure that the total of operating frequencies is less than total frequency.\n

• 2 phase 2 count input\n: [C251]\n30 kHz\n[C253 (OP), C252 to C255]\n5 kHz When\nusing multiple high-speed counters, ensure that the total operating frequency is less than the total frequency.\n

• Built-in pulse output / positioning function\n:\n

• Number of control axes\n: Independent 2 axes\n

• Maximum frequency\n: 100 kHz\n

• Programming language\n: Sequence program\n

• Corresponding basic unit\n: Transistor output type basic unit\n

• Pulse output instruction\n: 路 Pulse output (PLSY)\n路 Pulse output with acceleration / deceleration (PLSR)\nPulse output format: Pulse train (direction controlled by sequence)\n

• Positioning command\n: 路 ABS current reading ([D] ABS)\n路 Origin with DOG search [DSZR]\n路 Origin return [ZRN] (No DOG search function)\nDecelerates with near point DOG: ON and stops at near point DOG: OFF . (It differs from zero point return operation by counting the zero point signal)\n路 Variable speed pulse output [PLSV]\n路 Relative positioning [DRVI]\n路 Absolute positioning [DRVA]\nPulse output format: Pulse train + direction\n

• Ambient temperature\n: 0 to 55 掳 C. 路路路 Operating, -25 to 75 掳 C. 路路路路路 Save\n

• Relative humidity\n: 5 to 95% RH (noncondensing) 路 路 路 路 in operation\n

• Anti-vibration When DIN rail is installed( Frequency: 10 to 57 Hz)\n: One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The\ncriteria are based on IEC 61131-2\n

• Anti-vibration When DIN rail is installed (Frequency: 57 to 150 Hz)\n: Acceleration: 4.9 m / s 2 Ten times in each of X, Y, Z directions (total of 80 minutes each) The\ncriterion is based on IEC 61131-2\n

• Anti-vibration Direct installation ( Frequency: 10 to 57 Hz)\n: One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The\ncriteria are based on IEC 61131-2\n

• Anti-vibration Direct installation (Frequency: 57 to 150 Hz)\n: Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The\ncriteria are based on IEC 61131-2\n

• Impact resistance\n: 147 m / s 2 , working time 11 ms,\ncriterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2\n

• Noise immunity\n: Noise voltage with 1,000 Vp-p, noise width 1 碌s, rising 1 ns, with noise si

• tor with period of 30 to 100 Hz\n

• Withstand voltage\n: When performing the withstand voltage test, make the voltage between each terminal and the ground terminal of the basic unit with the following voltage.\nBetween the power supply terminal (AC power supply) and the earth terminal: AC 1.5 kV 1 minute\nDC 24 V service power supply and between the input terminal (24 VDC) and the earth terminal: 500 VAC for 1 min Between the\noutput terminal (transistor)\n

• Insulation resistance\n: When conducting the insulation resistance test, perform the following voltage between each terminal and the ground terminal of the basic unit.\nBetween the power supply terminal (AC power supply) and the earth terminal: 500\nVDC DC insulation resistance meter 5 MO or more DC 24 V service power supply, between the input terminal (24 VDC) and the earth terminal: 500 V DC 500 MO or more with the insulation resistance meter\nOutput terminal Between: 500 MV DC Insulation resistance meter 5 MO or more\n

• ground\n: Class D grounding (grounding resistance: 100 O or less) \nGrounding should be dedicated ground or common ground.\n

• Use atmosphere\n: There is no corrosive property, flammable gas, conductive dust (dust) is not serious\n

• Use altitude\n: It\ncan not be used under an environment pressurized to 2,000 m or less under atmospheric pressure. It may break down.\n

• \nPower Consumption (W): 21\n

• \nWeight (kg): 0.45\n

• \nDimensions (W x H x D) mm: 100 x 90 x 75\n

• \nShipping Weight : 1.5 Kg\n