FX3U-16CCL-M

$154.98

FX3U-16CCL-M -- Mitsubishi Electric -- CC-Link system master block FX 3 U - 16 CCL - M


• Estimated Lead Time : In stock. Usually ships in 5-7 working days.

• Manufacturer : Mitsubishi Electric

• CC-Link version : Ver.2.00 (Ver.1.10 is also supported)

• Station type : Master station (local station, standby master station function not available)

• Transmission speed : 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps selectable (set with rotary switch)

• Station number : 0 (set with rotary switch)

• Maximum cable total extension (maximum transmission distance) : Different according to transmission speed up to 1200 m

• Maximum number of connected stations Remote I / O station : Up to 8 stations (occupying the real I / O 32 points of the sequencer per one station)

• Remote device station + intelligent device station total : Up to 8 stations (total score of RX / RY is 256 or less each)

• Maximum input / output points per system FX3U / FX3UC PLC : Total of 1) + 2) = 384 1) (Sequencer real I / O points) + (Number of occupied I / O occupied points of special expansion block) + (Number of input / output occupied points of 16 CCL - M: 8 points) = 256 2) 32 number of stations of remote I / O station = 256 points

• FX 3 G / FX 3 GC Sequencer : 32 Number of stations of remote I / O station 128 points

• Number of links per station : 32 points Remote register (RWw): 4 points (Master station Remote device station / Intelligent device station) Remote register (RWr): 4 points (Remote device station / Intelligent device station Master Station) . The Above Is The Number Of Link Points In Remote Net Ver.1 Mode Refer To "FX 3 U - 16 CCL - M User 'S Manual (JY 997 D 43501)" For The Number Of Link Points In Remote Net Ver. 2 mode and Remote Net Addition mode.

• Communication method : Broadcast polling method

• Synchronization method : Frame synchronization method

• Coding scheme : NRZI system

• Transmission path format : Bus (RS-485)

• Transmission format : HDLC compliant

• Error control method : CRC (X 16 + X 12 + X 5 + 1)

• Connection cable : CC-Link dedicated cable / Ver. 1.10 compatible CC-Link dedicated cable CC-Link dedicated cable, CC-Link dedicated high-performance cable, Ver.1.10 compatible CC-Link dedicated cable It can Be Mixed Not. Also, Please Attach A Terminating Resistor Matching The Type Of Cable.

• RAS function : Automatic return function, Slave station detachment function, Abnormality detection by link special relay / register

• Communicate with the sequencer : Execute via buffer memory with FROM / TO instruction or direct specification of buffer memory (FX3U / FX3UC).

• Display (LED) : RUN, ERR., L RUN, L ERR. , SD, RD, POWER

• Number of occupied I / O points : 8 points (It can count either input or output)

• Application sequencer : FX3U -16CCL-M, FX2N-16CCL-M can not be used with FX2N-32ASI-M in combination with FX5U, FX5UC, FX3G, FX3U (Ver.2.20 or later), FX3GC, FX3UC (Ver.2.20 or later) .

• It is not possible to use FX 3 U - 16 CCL - M and FX 2 N - 16 CCL - M together.

• To connect to FX5U, FX5UC, FX5 - CNV - BUS or FX5 - CNV - BUSC is required. Depending on the system configuration, please choose either.

• To connect to FX 3 GC, FX 3 UC, FX 2 NC - CNV - IF or FX 3UC - 1 PS - 5 V is required.

• Mass : 0.3 kg

• Power supply specification

• Power supply External power supply : DC 24 V + 20% - 15% ripple (pp) within 5%

• Internal power supply : 5 V DC 5 V of the sequencer is not used. (24 VDC external power supply is converted to DC 5 V and power is supplied.) Please observe the power supply turning on timing and procedure and use it.

• Current consumption : 24 VDC external power supply: 240 mA

• Ambient temperature Relative humidity Impact resistance Noise immunity Withstand voltage Insulation resistance ground Use atmosphere Use altitude : 0 to 55 o C. &bull&bull&bull Operating -25 to 75 o C. &bull&bull&bull&bull&bull Save, : 5 to 95% RH (noncondensing)&bull&bull&bull&bull in operation.

• Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)

• Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)

• Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)

• Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)

• 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse

• Noise voltage with 1,000 Vp-p, noise width 1 us, rising 1 ns, with noise simulator with period of 30 to 100 Hz

• Between all terminals and ground terminal: 500 VAC for 1 minute

• Between all terminals and ground terminal: 500 MV DC 500 MO or more with an insulation resistance meter

• Class D grounding (grounding resistance: 100 O or less) Grounding must be dedicated ground or common ground.

• There is no corrosive property, flammable gas, conductive dust (dust) is not serious

• Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.

• Shipping Weight: 2 kg