FX3U-64CCL
$151.20
FX3U-64CCL -- Mitsubishi Electric -- Programmable Controllers MELSEC
• Estimated Lead Time : In stock. Usually ships in 5-7 working days.
• Manufacturer : Mitsubishi Electric
• CC-Link version : Ver.2.00 (Ver.1.10 is also supported)
• Station type : Intelligent device station
• Insulation method : The network bus and the internal power supply are photocoupler isolated
• Transmission speed : 156 Kbps / 625 Kbps / 2.5 Mbps / 5 Mbps / 10 Mbps
• Selectable (set with rotary switch)
• Station number : 1 to 64 stations (set with rotary switch)
• Number of occupied stations : 1 to 4 stations (set with rotary switch)
• Maximum cable total extension (maximum transmission distance) : According to CC-Link specification.
• Number of remote I / O points : The number of remote I / O points per station is 32 input points and 32 output points. (There is set by the extended cyclic setting of 1 to 8 times)
• However, the top 16 points of the final station will occupy the CC-Link system as a system area.
• Remote register point number : The number of remote registers per station is 4 RW write areas, 4 RW read areas. (There are 1 to 8 times setting depending on extended cyclic setting)
• Communication method : Broadcast polling method
• Synchronization method : Flag synchronization method
• Coding scheme : NRZI system
• Transmission path format : Bus (RS-485)
• Transmission format : HDLC compliant
• Error control method : CRC (X 16 + X 12 + X 5 + 1)
• Connection cable : CC-Link dedicated cable, CC-Link exclusive high-performance cable, Ver. 1.10 compatible CC-Link dedicated cable
• cable can not be mixed.
• Communicate with the sequencer : Perform through the buffer memory with the FROM / TO instruction (or directly designate the buffer memory)
• Display (LED) : RD, SD, RUN, ERR., L RUN, L ERR., POWER
• Number of occupied I / O points : 8 points (It can count either input or output)
• Application sequencer : FX5U, FX5UC, FX3G, FX3U, FX3GC, FX3UC (Ver. 2.20 SER No.55 **** after May 2005 product)
• * You can connect only one 64CCL to one sequencer basic unit. To connect to FX5U, FX5UC, FX5 - CNV - BUS or FX5 - CNV - BUSC is required. Depending on the system configuration, please choose either. To connect to FX 3 GC, FX 3 UC, FX 2 NC - CNV - IF or FX 3UC - 1 PS - 5 V is required.
• mass : 0.3 kg
• Power supply : DC 5 V internal power supply: DC 5 V of the programmable controller is not used. (DC 5 V is converted from 24 VDC external power supply)
• 24 VDC external power supply: Power is supplied from the external terminal block. (+ 20% - 15% ripple (pp) within 5%)
• Allowable momentary power outage time : PS 1: Continue operation against momentary power failure of 1 ms or less
• Current consumption : 220 mA
• Ambient temperature : 0 to 55 掳 C. 路路路 Operating -25 to 75 掳 C. 路路路路路 Save
• Relative humidity : 5 to 95% RH (noncondensing) 路 路 路 路 in operation
• Anti-vibration When DIN rail is installed Frequency: 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
• Frequency: 57 to 150 Hz : Acceleration: 4.9 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total)
• Direct installation Frequency: 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
• Frequency: 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
• Impact resistance : 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
• Noise immunity : Noise voltage with 1,000 Vp-p, noise width 1 碌s, rising 1 ns, with noise simulator with period of 30 to 100 Hz
• Withstand voltage : Between all terminals and ground terminal: 500 VAC for 1 minute
• Insulation resistance : Between all terminals and ground terminal: 500 MV DC 500 MO or more with an insulation resistance meter
• ground : Class D grounding (grounding resistance: 100 O or less) <Common grounding with high voltage system is not allowed>
• Grounding must be dedicated ground or common ground.
• Use atmosphere : There is no corrosive property, flammable gas, conductive dust (dust) is not serious
• Use altitude : Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
• Shipping Weight: 2 kg