Q64TCRTBW
$544.50
Temperature control unit Q64TCRTBW
• Estimated Lead Time : In stock. Usually ships in 7-10 working days.
• Manufacturer : Mitsubishi Electric
• Q64TCRTBW
• Temperature control unit Q64TCRTBW
• Control output : Transistor output
• Number of temperature input points : 4 channels / unit
• Usable resistance temperature detector : Pt 100, JPt 100
• accuracy Instruction accuracy Ambient temperature: 25 卤 5 掳 C : Full scale X (卤 0.3%)
• Ambient temperature: 0 to 55 掳 C : Full scale X (卤 0.7%)
• Sampling cycle : 500 ms / 4 channels
• Control output period : 1 to 100 s
• Input impedance : 1 M惟
• Input filter : 0 to 100 s (0: input filter OFF)
• Sensor correction value setting : -50.00 to 50.00%
• Operation at sensor input disconnection : Upscale processing
• Temperature control system : PID ON / OFF pulse or 2 position control
• PID constant range PID constant setting : Setting by auto tuning is possible
• Proportional band (P) : 0.0 to 1000.0% (0.0: 2 position control)
• Integration time (I) : 1 to 3600 s
• Differential time (D) : 0 to 3600 s (0: PI control)
• Target value setting range : Within the temperature range set by the platinum resistance bulb to be used
• Dead band setting range : 0.1 to 10.0%
• Transistor output Output signal : ON / OFF pulse
• Rated load voltage : 10 to 30 VDC
• Maximum load current : 0.1 A / 1 point, 0.4 A / 1 common
• Maximum inrush current : 0.4 A, 10 ms
• Leakage current at OFF : 0.1 mA or less
• Maximum voltage drop during ON : DC 1.0 V (TYP.) 0.1 A, DC 2.5 V (MAX.) 0.1 A
• Response time OFF ??ON : 2 ms or less
• ON ??OFF : 2 ms or less
• Insulation method : Input and ground, between input channels: Transformer insulation
• Withstand voltage : Between input and ground, between input channels: 500 VAC for 1 minute
• Insulation resistance : Between input and ground, between input channels: DC 500 V 20 M惟 or more
• Heater disconnection detection specification Current sensor : CTL - 6 - P (0.00 to 20.00 A) CTL - 6 - PH (0.00 to 20.00 A) CTL - 12 - S36 - 8 (0.0 to 100.0 A) produced by Earl Dee Co.,
• Input accuracy : Full scale X (卤 1.0%)
• Number of alarm delay times : 3 to 255
• External wiring connection method : 18 point screw terminal block (M3 screw) X 2
• Number of occupied I / O points : 32 points, 2 slots (I / O assignment: 16 free points + 16 points of intelligence)
• DC 5 V Internal current consumption : 0.64 A
• External dimensions Height (H) : 98 mm
• Width (W) : 55.2 mm
• Depth (D) : 112 mm
• mass : 0.30 Kg
• Shipping Weight : 1.3 Kg