QD81DL96
$1,062.18
High-speed data logger unit QD81DL96
• Estimated Lead Time : In stock. Usually ships in 7-10 working days.
• Manufacturer : Mitsubishi Electric
• QD81DL96
• High-speed data logger unit QD81DL96
• Software specification :
• Data collection Number of CPUs to be accessed : Up to 64
• Collection interval High speed collection : ??Sequence scan time synchronization ??1 to 32767 ms (at trigger logging) ??3 to 32767 ms (continuous logging)
• General purpose collection : ??0.1 to 0.9 s, 1 to 32767 s ??Time interval specification (hour, minute, second designation)
• Number of collected data High speed collection : . Total number of data: Maximum 8192 (per setting: 256) . Total number of device points: Up to 8192 (per setting: 256)
• General purpose collection : . Total number of data: Maximum 16384 (per setting: 256) . Total number of device points: Up to 262144 (per setting: 4096)
• Data type : ??Bit word (signed) ??Double word (signed) ??Word (unsigned) ??Double word (unsigned) ??Single precision real number ??Double precision real number ??16 bit BCD ??32 bit BCD ??String: 1 to 8192 characters . Number string: 1 to 8192 bytes
• Data output format (CSV file) : . Bit . Decimal format: Number of digits after the decimal point 0 to 14 . Exponential format: Number of digits after the decimal point 0 to 14 . Hexadecimal format . String . Numeric string
• scaling : Arithmetic operations: combination operation of (X, 梅) and (+, -)
• Data logging Number of settings : Up to 64
• Logging type : . Continuous logging . Trigger logging
• file format : . CSV file (extension: .CSV) . Binary file (extension: .BIN)
• period : Specify the corresponding period or exclusion period. . Data condition: Bit ON / OFF, comparison of data and constant value, comparison of data and data . Date range: start date and end time as month . day designation . time range: hour, minute, second designation as day of week / Week condition: Specify day of week and week Specify the above AND or OR combination: Up to 8 conditions
• Trigger logging Trigger condition : . Condition: . Comparison: Bit ON / OFF, comparison of data and constant value, comparison between data and data . Value change . Constant period: 1 to 86400 s . Time interval designation: hour, minute, second . Time designation: month . Days . Hour . Minutes . Second designation . Unit activation time above AND or OR combination (Up to 8 conditions) . Number of conditions fulfilled: 3 conditions . Condition establishment order (order and time condition): up to 4 conditions
• Number of logging lines : ??Before trigger generation: 0 to 65534 lines ??After trigger generation: 1 to 65535 lines Before the trigger occurred, up to 65535 lines after the trigger occurrence
• File switching timing : . Number of lines (number of records) specification: 100 ~ 100000 lines . File size designation: 10 ~ 16384 Kbytes . Condition specification: . Comparison: Bit ON / OFF, comparison of data and constant value, comparison between data and data . Value change . Constant period: 1 to 86400 s . Time interval designation: hour, minute, second designation . Time designation: Monday . Day . Hour . Minute . Second designation . Unit start time AND or OR combination above: Up to 8 conditions . Trigger logging unit
• Number of files saved : 1 to 65535
• Event logging Number of settings : Up to 64
• Number of events : Up to 64 per event logging setting
• file format : . CSV file (extension: .CSV) . Binary file (extension: .BIN)
• Event condition : . Condition: . Comparison: Bit ON / OFF, comparison of data and constant value, comparison between data and data . Value change above AND or OR combination above: up to 4 conditions . Number of conditions fulfilled: 3 conditions . Condition establishment order And time condition): up to 4 conditions
• period : Specify the corresponding period or exclusion period. . Data condition: Bit ON / OFF, comparison of data and constant value, comparison of data and data . Date range: start date and end time as month . day designation . time range: hour, minute, second designation as day of week / Week condition: Specify day of week and week Specify AND or OR combination above: Up to 8 conditions
• File switching timing : . Number of lines (number of records) specification: 100 ~ 100000 lines . File size designation: 10 ~ 16384 Kbytes . Condition specification: . Comparison: Bit ON / OFF, comparison of data and constant value, comparison between data and data . Value change . Constant period: 1 to 86400 s . Time interval designation: hour, minute, second designation . Time designation: Monday . Day . Hour . Minute . Second designation . Unit startup The above AND or OR combination (up to 8 conditions)
• Number of files saved : 1 to 65535
• Report Number of settings : Up to 64
• file format : Excel庐 file (extension:. Xls)
• Output data type : . Data in the data logging file . Current value data . Creation time
• Number of output data : 64 layouts per report setting, total 65535 cells
• Creation trigger condition : . Condition: . Comparison: Bit ON / OFF, comparison of data and constant value, comparison of data and data . Value change . Constant period: 1 to 86400 s . Time interval designation: hour, minute, second designation . Time designation: month . Date / hour / minute / second designation . When unit is started . When data logging file is changed . The above AND or OR combination (Up to 8 conditions) . Number of condition establishment times: 3 conditions . Condition establishment order (order and time condition): 4 conditions Until
• period : Specify the corresponding period or exclusion period. . Data condition: Bit ON / OFF, comparison of data and constant value, comparison of data and data . Date range: start date and end time as month . day designation . time range: hour, minute, second designation as day of week / Week condition: Specify day of week and week Specify the above AND or OR combination: Up to 8 conditions
• Layout file size : Up to 10 Mbytes (Total of all report settings)
• Number of files saved : 1 to 65535
• e-mail Use : . Notification of event occurrence . Sending of stored file
• Subject (subject) : . Event notification mail: User specification . Save file send mail: Automatic creation / user specification
• Text : . Event notification mail: User specification . Save file send mail: Automatic creation / user specification
• Attachment : . Event notification mail: None . Save file transmission mail: Save file (CSV, binary, Excel file), maximum 512 KB
• Attachment file format : MIME format
• MIME : Version 1.0
• Communicate with mail server port number : 25, 587, others (1 to 65535)
• Authentication method : - No authentication - SMTP - AUTH (PLAIN, LOGIN, CRAM - MD 5) - POP before SMTP
• Destination address : Up to 16 groups
• Operation confirmation mail client software : . Microsoft 庐 Outlook 庐 Express 6.0 . Microsoft 庐 Windows 庐 Mail 6.0
• FTP server Use : Reading and deleting saved files, writing, reading, and deleting recipe files
• Operation check FTP client software : . Microsoft庐 Internet Explorer庐 6.0 . Windows庐 Internet Explorer庐 7.0 . Windows庐 Internet Explorer庐 8.0 . Windows庐 Internet Explorer庐 9.0 . Windows庐 Internet Explorer庐 10.0 . Windows庐 Internet Explorer庐 11.0
• Number of visits : Ten
• FTP client Use : Transfer file saved
• Operation check FTP server software : Microsoft庐 Internet Information Services
• recipe The number of data : Up to 256 data
• Number of records : Up to 256 records
• Data type : . Bit word . Signed . Double word . Signed . Word [unsigned] . Double word [unsigned] . Single precision real number . Double precision real number . 16 bit BCD . 32 bit BCD
• Recipe file : CSV file (extension: CSV) Up to 256 files
• Execution type : Dedicated instruction (ladder program), setting tool
• Hardware specification :
• Ethernet section interface : 10 BASE-T / 100 BASE-TX
• Communication method : Full duplex / half duplex communication mode
• Flow control : Full duplex communication: None (IEEE802.3x flow control is not supported) Half duplex communication: back pressure
• Data transmission speed : 10 Mbps (10 BASE-T) / 100 Mbps (100 BASE-TX)
• Transmission method : Baseband
• Number of cascade connection stages : Up to 4 stages (10 BASE - T) / 2 stages maximum (100 BASE - TX)
• Maximum segment length : 100 m
• Support function : Auto negotiation function (communication speed / communication method automatic recognition)
• CompactFlash card part Supply power capacity : Maximum 150 mA
• Card size : TYPE I card
• Supply power supply voltage : 3.3 V 卤 5%
• Number of installable sheets : 1 sheet
• Number of occupied I / O points : 32 points (I / O assignment: 32 points of intelligence)
• clock : . Accuracy of time after obtaining / obtaining from PLC CPU (Unit 1 CPU in multi CPU system) or SNTP server is 卤 9.504 seconds
• DC 5 V Internal current consumption : 0.50 A
• External dimensions Height (H) : 98 mm
• Width (W) : 27.4 mm
• Depth (D) : 90 mm
• mass : 0.15 Kg
• Shipping Weight : 1.2 Kg